Standard EN60903
Live Working Gloves of Insulating Material

Standard EN374 Resistance to Water PenetrationTo obtain compliance with EN60903, all gloves must be tested to the relevant voltage in the table shown. The construction, thickness and test voltage combine to give the class compliance. To maintain compliance, gloves must be inspected and/or re-tested every 6 months.

A/C

Class Testing Voltage Maximum Working Voltage
0 2,500V 500V
0 5,000V 1,000V
1 10,000V 7,500V
2 20,000V 17,000V
3 30,000V 26,500V
4 40,000V 36,000V

D/C

Class Testing Voltage Maximum Working Voltage
0 4,000V 750V
0 10,000V 1,500V
1 20,000V 11,250V
2 30,000V 25,500V
3 40,000V 39,750V
4 60,000V 54,000V

 

 


SSL site seal - click to verify
We use cookies to enhance your experience. Find out more > Close